SUPERIORTM GSA Chlorinator Series CLM-1
Direct Cylinder Mounted-All Vacuum
|
|
| |
| |
GENERAL
DESCRIPTION
The SUPERIORTM Series CLM-1 Gas Chlorinator
is a state-of-the-art, vacuum-operated, solution feed
type which mounts directly on a chlorine valve using a
very heavy-duty, positive yoke clamp connection. A chlorine
gas flow meter indicates the amount of chlorine being
fed. Chlorine flow rate is manually adjusted and the design
permits easy addition of a number of automatic flow rate
control devices. A high efficiency, |
| water operated ejector produces
the vacuum necessary to operate the system. The ejector
assembly contains a back-flow check valve system to prevent
pressurized water from entering the chlorinator. A spring-opposed
diaphragm vacuum regulator controls the chlorine gas flow
rate and also acts as the safety shut-off valve. |
|
|
|
FEATURES |
THE SUPERIORTM Series CLM-1 presents
the most modern design technology coupled with the very best
materials available to create an outstanding, user friendly
piece of equipment. It is designed with user safety as a primary
concern. 1.
A new ultra-thick, fluoroplastic yoke coating gives SUPERIORTM
corrosion resistance, won’t crack, peel or chip. Chlorine will
not diffuse through it to cause coating bubbling and peeling.
2. All molded parts
are fiber-glass reinforced ABS plastic, designed for SUPERIORTM
strength, warp-resistance and chlorine resistance. 3.
The rate valve “seat” is pure fluoroplastic and will not swell,
stick or become brittle with age or exposure to liquid chlorine.
4. All external bolts and nuts are
Titanium for complete corrosion resistance..a SUPERIORTM exclusive
There are no stainless steel or monel nuts and bolts to corrode
and freeze up in the presence of moist chlorine gas. 5.
Extra heavy-duty outlet threads on the ejector diffuser prevents
accidental breakage from over-tightening or “bumping” of the
ejector assembly. 6.
The “Universal” ejector diffuser allows use of high pressure
solution hose, direct ejector mounting in mains, or in-line
piping with rigid solution pipe. 7.
Easier to service and perform routine maintenance, with standard
size wrench lugs provided on all screwed-together ejector parts.
No more pipe wrenches to accidentally tear and scrape plastic
surfaces. 8.
All vacuum fitting holes are heavily reinforced to prevent the
possibility of cracking from over-tightening fittings. 9.
“dual-pressure” check valve is standard on all SUPERIORTM gas
Chlorinators. Proven high back-pressure unitized check valve
design protects against sudden surges up to 300 PSIG while a
spring-loaded diaphragm check provides positive shut off even
when there is no back-pressure to force the seat closed.
10. PVDF vacuum
tubing fitting s are standard. another SUPERIORTM exclusive.
“User friendly” design makes it easy to attach tubing, and to
tighten or loosen ferrule nuts without tools. 11.
Fewer parts, combined with superior materials and a superior
design gives you a SUPERIORTM Gas Chlorinator. |
| FLOW
METER CAPACITIES |
| Variable area flow metering tubes are available
with dual English/Metric scale mazimum capacities of 0.8,1.5,4,10,25,50
and 100 pounds per 24 hours of chlorine gas,as well as 15,30,75,200,500,1000
and 2000 grams per hour, respectively. All metering tubes are
interchangeable and may be changed in the field without special
tools. |
| MODULAR
DESIGN |
| SUPERIORTM Gas Chlorinators have been
designed to give the maximum flexibility in system installation.
The vacuum regulator and metering tube panel are close coupled
and mounted onto the chlorine cylinder value as a single assembly.
The ejector can be located wherever plumbing and/or hydraulic
conditions make it most desirable. Modular design also makes
it easy and inexpensive to expand or upgrade the system. The
metering tube panel may be detached from the vacuum regulator
at any time, in just a few minutes, if future requirements or
safety dictate a remote metering application, or multiple point
chlorination is desired. |
| MATERIALS OF CONSTRUCTION |
| One of SUPERIOR’S major competitive
advantages is the use of the finest, strongest and most durable
materials available. Extensive use of Fluoroplastics and fiberglass
reinforced thermoplastics allow SUPERIORTM Gas Chlorinators
to withstand attack by chlorine in any form and to give the
longest operational lift. Many parts are guaranteed for the
lift of the equipment against chlorine damage. |
| SYSTEM OPERATION |
The vacuum regulator is securely clamped
onto the chlorine cylinder valve. Water under pressure flows
through the ejector at high velocity which causes a strong vacuum
to be created. This opens the check valves in the ejector assembly
and transmits a vacuum signal through the meter tube/rate valve
panel back to the vacuum regulator. When the vacuum reaches
a pre-set level, the diaphragm in the regulator moves to open
the chlorine inlet safety valve, permitting gas to flow from
the chlorine cylinder. The spring-opposed diaphragm and inlet
valve regulate the vacuum at this point.
Chlorine gas passes through the flow meter panel and rate control
valve to the ejector. The gas mixes with the ejector water and
is discharged through the diffuser into the water being treated. |
|
|
| SPECIFICATIONS |
The chlorinator shall be SUPERIORTM
MODEL CLM-1 manufactured by Chemical Injection Technologies,
Inc.,FT. Pierce, Florida, and shall have a maximum capacity
of pounds per day (gr/hr) of chlorine feed and shall be equipped
with a chlorine flow meter of pounds per day (gr/hr).
The chlorinator shall consist of a close-coupled vacuum regulator/flow
meter, and ejector/check valve. Each of these assemblies shall
be capable of being individually located wherever safety and/or
operator convenience dictated. The vacuum reguator/flow meter
assembly shall be capable of being separated into independent
vacuum regulator and metering panel assemblies at any time for
remote metering or multiple point chlorination applications.
The vacuum regulator/flow meter shall mount directly on the
chlorine valve by means of a positive yoke clamp having an integral
tightening screw with slide bar handle. No wrenches or other
tools shall be required to mount or dismount the vacuum regulator
from the chlorine. The cylinder valve/chlorinator inlet adaptor
shall be constructed of corrosion-proof fluoroplastic material
which shall be inert to the effects of wet, dry or liquid chlorine.
The inlet safety shut-off/vacuum regulating valve shall be of
capsulated design, easily removable as a unit from the vacuum
regulator inlet and shall be capable of removing impurities
greater than 25 microns. A pressure relief valve shall be incorporated
into the vacuum regulator to prevent pressure from building
up in the system. All external screws and nuts shall be made
of Titanium to prevent corrosion.
The vacuum regulator/flow meter bodies shall be constructed
of fiberglass reinforced thermoplastic material and shall incorporate
a flow rate control valve made of fluoroplastic material which
is inert to the corrosive effects of chlorine. The rate valve
metering tip shall be constructed of pure silver. Design shall
provide for full closing of the rate valve without engaging
the control surfaces, to prevent damage.
Vacuum shall be created by a fixed-throat venture/ejector system
connected directly to the chlorine solution diffuser. A dual
high-pressure/low-pressure check valve system shall prevent
water from entering the gas system. The ejector assembly shall
be capable of withstanding water pressure up to 300 PSIG(20.7
Bars). A universal-type chlorine solution diffuser shall be
provided which shall allow close-coupling of the ejector to
a water main, use of flexible solution hose or rigid solution
pipe without the use of special adaptors. |
| STANDARD ACCESSORIES |
25 ft.- 3/8 Vent & vacuum tubing
10-Lead cylinder connection gaskets
1-Cylinder Wernch
1-Vent insect screen |
| OPTIONAL ACCESSORIES
AVAILABLE |
Inlet Water Assembly Gas Masks
Wall manifold kits Gas Detectors
Booster pumps Scales
Residual Analyzers Gauges
Automatic Controls Chlorine Comparators
Ton Container Adaptors Others Available |
| OTHER SUPERIORTM
SYSTEMS AVAILABLE |
AUTOMATIC SWITCHOVER GAS CHLORINATORS
MULTIPLE-POINT GAS CHLORINATORS
200 POUNDS PER DAY(5 kg/HR)
500 POUNDS PER DAY (10 KG/HR)
GAS SULFONATORS (DECHLORINATOR)
AMMONIATORS
AUTOMATIC FLOW PROPORTIONING
AUTOMATIC RESIDUAL CONTROL |
|